Products
----------------------------------------
-
Wall Mounted
----------------------------------------
-
Wall Mounted I.A.Q.
----------------------------------------
-
Multi-Zone
----------------------------------------
- Cassette
----------------------------------------
-
Large
Ceiling
----------------------------------------
-
Universal Floor / Ceiling
----------------------------------------
 |

|
Products > Cassette |
 |
Cassette
 |
|

Indoor Unit
|

Outdoor Unit
Systems: 18RCLX, 24RCLX, 36RCLX
|

Outdoor Unit
System 42RCLX |
|
Extremely
discreet, with only the grill showing in the ceiling.
Latest fan
technology distributes the conditioned air evenly throughout the room.
Ceiling cassette systems provide both heating and cooling and are popular
in commercial applications such as offices, conference rooms, restaurants,
night clubs and bars, as well as new construction condominiums and homes. |

Energy
Calculator

Ask
Fujitsu
 |
 |
|
SYSTEM |
18RCLX |
24RCLX |
36RCLX |
42RCLX |
|
CAPACITIES: |
|
Cooling
BTU/h |
17,800 |
22,200 |
34,100 |
42,700 |
Outdoor
Design Temp
F° DB/WB |
95/75 |
95/75 |
95/75 |
95/75 |
|
Heating
BTU/h |
21,000 |
24,200 |
36,000 |
45,200 |
Outdoor
Design Temp
F° DB/WB |
47/43 |
47/43 |
47/43 |
47/43 |
|
SEER |
16 |
15 |
14 |
15 |
|
EER Clg/Htg |
11.1/10.2 |
10.6/10.2 |
8.1/9.7 |
9.2/10.5 |
|
HSPF |
8.5 |
8.5 |
8.5 |
8.5 |
|
Power
Supply (V) |
208-230 |
208-230 |
208-230 |
208-230 |
|
INDOOR
UNIT: |
Noise
Level db (A) Cooling
Hi
Med
Lo |
42
39
36 |
45
43
38 |
48
45
41 |
50
48
44 |
Noise
Level db (A) Heating
Hi
Med
Lo |
40
38
36 |
43
39
35 |
48
45
31 |
50
48
44 |
|
Weight
(lbs.) |
75 |
75 |
82 |
88 |
|
OUTDOOR
UNIT: |
|
Max
Fuse Size (A) |
20 |
20 |
30 |
30 |
|
Min. Ampacity (A) |
15.4 |
15.4 |
23 |
26 |
|
Running
Current Clg (A) Rated/Max |
7.0/12.5 |
9.2/12.5 |
18.3/18.8 |
20.3/21.7 |
|
Running
Current Htg (A) Rated/Max |
8.9/12.5 |
10.4/12.5 |
16.2/18.8 |
19.1/21.7 |
|
Weight
(lbs.) |
141 |
141 |
141 |
231 |
|
REFRIGERANT PIPING: |
|
Max Ht.
Difference (ft.) |
65 |
65 |
98 |
98 |
Max
Total or Combined
Length (ft.) |
165 |
165 |
165 |
230 |
Discharge Vapor Line
(O.D.) inches |
1/4 |
3/8 |
3/8 |
3/8 |
|
Suction
(O.D.) inches |
1/2 |
5/8 |
5/8 |
5/8 |
|
| |
|