Cooling  35,200 BTU/h
Heating  36,400 BTU/h

Specification
Power Source Voltage/Frequency/Phase 208-230/60/1
Connectable Indoor Unit Number 2 to 3
Connectable Unit Capacity Class BTU/h 14 to 27,000
Rated Capacity Cooling/Heating BTU/h 35,200/36,400
Operation Range Cooling °F(°C) 14 to 115
(-10 to 46)
Heating -15 to 75
(-26 to 24)
Input Power: Clg/Htg Rated kW 1.65/1.81
Current: Total Max. A 20.8
Minimum Circuit Ampacity A 25.1
MAX.CRT.BKR A 30
Outdoor Fan Airflow CFM Clg/Htg 1,942/1,942
Fan: Type × Quantity Propeller × 1
Sound Pressure Level Cooling dB(A) 50
Heating 52
Pre-Charge Length Total Ft (m) 98 (30)
Max. Length Total 230 (70)
Length Each 82 (25)
Min. Length Total 49 (15)
Length Each 16 (5)
Max. Pipe Height Difference Between Outdoor Unit & Farthest Indoor Ft (m) 49 (15)
Indoor Units 33 (10)
Connection Method Flare
Conn. Pipe Diameter Inch Liq. 1/4 x 3
Suc. 1/2 x 1,
3/8 x 2
Net Weight lbs. (kg) 146 (66)
Dimensions Height Inch 32-11/16
mm 830
Width Inch 35-7/16
mm 900
Depth Inch 13
mm 330
Refrigerant (Global Warming Potential) R410A