Heat Pump Type V-II Series AOUA288RLBVG1  [3Phase]

Outdoor unit

Outdoor Unit :
AOUA288RLBVG1
Download :
Catalog

Features

  • Operational efficiency
  • Energy saving technology

Capacity

Cooling  288,000 BTU/h
Heating  324,000 BTU/h


Specification

Rating Capacity Range 24
Maximum Connectable Indoor Unit 45
Scroll
Power source Phase 3-phase
Voltage 208 / 230 V
Frequency 60 Hz
Capacity Cooling 288,000 BTU/h
84.4 kW
Heating 324,000 BTU/h
95.0 kW
Input Power Cooling 25.27 kW
Heating 26.28 kW
EER (Non-Ducted/Ducted) Cooling 10.6 / 10.6 Btu/hW
IEER (Non-Ducted/Ducted) Cooling 20.8 / 20.1 Btu/hW
COP (Non-Ducted/Ducted) Heating 3.36 / 3.31 W/W
Air Flow Rate 3×6,533 CFM (3×11,100 m³/h)
Sound Pressure Level Cooling 64 dB(A)
Heating 64 dB(A)
Maximum external static pressure 0.32 in.WG (80 Pa)
Compressor motor output 3×7.5 kW
Net Dimensions Height 66-9/16 inch (1,690 mm)
Width 3×(36-5/8) inch (3×930 mm)
Depth 30-1/8 inch (765 mm)
Net Weight 3×564 lbs (3×256 kg)
Refrigerant Type R410A
Charge 3×25.79 lbs (3×11.7 kg)
Connection Pipe Diameter Liquid 3/4 inch (19.05 mm)
Discharge Gas 1-3/8 inch (34.92 mm)
Operation Range Cooling 23 to 115 °FDB (-5 to 46 °CDB)
Heating -4 to 70 °FDB (-20 to 21 °CDB)
Scroll
Note :
Specifications are based on the following conditions.
Cooling :
Indoor temperature of 80°F (26.7°C) DB / 67°F (19.4°C) WB, and outdoor temperature of 95°F (35.0°C) DB / 75°F (23.9°C) WB.
Heating :
Indoor temperature of 70°F (21.1°C) DB / 60°F (15.6°C) WB, and outdoor temperature of 47°F (8.3°C) DB / 43°F (6.1°C) WB.
Pipe length :
25ft. (7.5 m); Height difference between outdoor unit and indoor unit : 0ft. (0 m).
*1
Electrical data is only for outdoor unit.

Dimensions

Outdoor Unit : AOUA288RLBVG1

Outdoor unit