Heat Pump Type V-II Series AOUA288RLBVG1 [3Phase]
Specification
Rating Capacity Range | 24 |
---|---|
Maximum Connectable Indoor Unit | 45 |
Scroll
Power source | Phase | 3-phase |
---|---|---|
Voltage | 208 / 230 V | |
Frequency | 60 Hz | |
Capacity | Cooling | 288,000 BTU/h |
84.4 kW | ||
Heating | 324,000 BTU/h | |
95.0 kW | ||
Input Power | Cooling | 25.27 kW |
Heating | 26.28 kW | |
EER (Non-Ducted/Ducted) | Cooling | 10.6 / 10.6 Btu/hW |
IEER (Non-Ducted/Ducted) | Cooling | 20.8 / 20.1 Btu/hW |
COP (Non-Ducted/Ducted) | Heating | 3.36 / 3.31 W/W |
Air Flow Rate | 3×6,533 CFM (3×11,100 m³/h) | |
Sound Pressure Level | Cooling | 64 dB(A) |
Heating | 64 dB(A) | |
Maximum external static pressure | 0.32 in.WG (80 Pa) | |
Compressor motor output | 3×7.5 kW | |
Net Dimensions | Height | 66-9/16 inch (1,690 mm) |
Width | 3×(36-5/8) inch (3×930 mm) | |
Depth | 30-1/8 inch (765 mm) | |
Net Weight | 3×564 lbs (3×256 kg) | |
Refrigerant | Type | R410A |
Charge | 3×25.79 lbs (3×11.7 kg) | |
Connection Pipe Diameter | Liquid | 3/4 inch (19.05 mm) |
Discharge Gas | 1-3/8 inch (34.92 mm) | |
Operation Range | Cooling | 23 to 115 °FDB (-5 to 46 °CDB) |
Heating | -4 to 70 °FDB (-20 to 21 °CDB) |
Scroll
- Note :
- Specifications are based on the following conditions.
- Cooling :
- Indoor temperature of 80°F (26.7°C) DB / 67°F (19.4°C) WB, and outdoor temperature of 95°F (35.0°C) DB / 75°F (23.9°C) WB.
- Heating :
- Indoor temperature of 70°F (21.1°C) DB / 60°F (15.6°C) WB, and outdoor temperature of 47°F (8.3°C) DB / 43°F (6.1°C) WB.
- Pipe length :
- 25ft. (7.5 m); Height difference between outdoor unit and indoor unit : 0ft. (0 m).
- *1
- Electrical data is only for outdoor unit.